Technical dataKL3214
Number of inputs 4
Power supply via the K-bus
Input filter limit frequency typ. 1 kHz
Sensor types Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, potentiometer: 10 Ω…1.2/4 kΩ, KTY sensors (types see documentation)
Measuring range -200…+850°C (Pt sensors), -60…+250°C (Ni sensors)
Connection method 3-wire
Conversion time approx. 170 ms default setting
Measuring current
Resolution 0.1В°C per digit
Measurement error/uncertainty
Electrical isolation 500 V (K-bus/signal voltage)
Current consumption power contacts –
Current consumption K-bus typ. 120 mA
Special features open-circuit recognition
Weight approx. 60 g
Operating/storage temperature 0…+55°C/-25…+85°C
Relative humidity 95%, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos. IP20/variable
Approvals/markings CE, UL