| Number of inputs | 2 |
| Power supply | via the K-bus |
| Technology | 2-wire |
| Thermocouple sensor types | types J, K, L, B, E, N, R, S, T, U (default setting type K), mV measurement |
| Measuring range | in the range defined in each case for the sensor (default setting: type K, -100…+1370°C), mV measurement: ±30 mV…±120 mV |
| Connection method | 2-wire |
| Conversion time | ~ 250 ms |
| Wiring fail indication | yes |
| Resolution | 0.1В°C per digit |
| Measurement error/uncertainty | |
| Electrical isolation | 500 V (K-bus/signal voltage) |
| Current consumption power contacts | – (no power contacts) |
| Current consumption K-bus | typ. 65 mA |
| Bit width in the process image | input: 2 x 16В bit data (2 x 8В bit control/status optional) |
| Configuration | no address setting, configuration via Bus Coupler or controller |
| Weight | approx. 70 g |
| Operating/storage temperature | 0…+55°C/-25…+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/variable |
| Approvals/markings | CE, UL, ATEX, IECEx |
| Ex marking | ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc |