| Connection technology | 2-/3-/4-wire |
| Number of outputs | 1 x make contact |
| Nominal voltage | 0…230 V AC/DC |
| Load type | ohmic, inductive |
| Max. output current | 3 A steady load |
| Surge voltage protection | from 400 V AC |
| Peak current | 5 A (20 s), 50 A (100 ms) |
| Switching current | peak current: 5 A (20 s), 50 A (100 ms) |
| Recommended fuse | ≤ 10 A fast fuse |
| Contact resistance | 0.1 О© typ. |
| Switch-off time | 2…4 ms |
| Residual voltage | (100 mО©) |
| Electrical isolation | 500 V (K-bus/field voltage), 2500 V AC (1 min.) |
| Leakage current (OFF state) | |
| Switching speed | typ. 1.65 ms, 5 ms max. |
| Current consumption power contacts | only leakage and load current |
| Current consumption K-bus | typ. 65 mA |
| Bit width in the process image | 2 outputs |
| Configuration | no address or configuration setting |
| Weight | approx. 55 g |
| Operating/storage temperature | 0…+55°C/-25…+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/variable |
| Pluggable wiring | for all KSxxxx Bus Terminals |
| Approvals/markings | CE |