Каталог

Technical dataKL2652
Number of outputs 2 x change-over
Nominal voltage 230 V AC (max. switching voltage 250 V AC/300 V DC)
Switching voltage max. 250 V AC, 300 V DC
Load type ohmic, inductive, lamp load
Max. output current 5 A per channel
Switching current max. 1 A AC/1 A DC at 40 V DC, max. 0.15 A at 300 V DC (UL: max. 230 V AC, 1 A)
Minimum permitted load 100 mA at 12В V
Lamp test, electronic ballast max. 6 A starting current
Electrical isolation 1.5 kV (K-bus/field potential), 2.5 kV rated surge voltage, overvoltage category III
Current consumption power contacts –
Current consumption K-bus typ. 90 mA
Bit width in the process image 2 outputs
Max. switching frequency 6/min. (at rated load)
Operating cycles mech. (min.) 5 x 106
Operating cycles electr. (min.) 1 x 106 (1В A/250В VВ AC)
Configuration no address or configuration setting
Special features reverse switching realizable
Weight approx. 55 g
Operating/storage temperature 0…+55°C/-25…+85°C
Relative humidity 95%, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos. IP20/variable
Pluggable wiring for all KSxxxx Bus Terminals
Approvals/markings CE, UL