| Number of outputs | 2 x change-over |
| Nominal voltage | 230 V AC (max. switching voltage 250 V AC/300 V DC) |
| Switching voltage max. | 250 V AC, 300 V DC |
| Load type | ohmic, inductive, lamp load |
| Max. output current | 5 A per channel |
| Switching current | max. 1 A AC/1 A DC at 40 V DC, max. 0.15 A at 300 V DC (UL: max. 230 V AC, 1 A) |
| Minimum permitted load | 100 mA at 12В V |
| Lamp test, electronic ballast | max. 6 A starting current |
| Electrical isolation | 1.5 kV (K-bus/field potential), 2.5 kV rated surge voltage, overvoltage category III |
| Current consumption power contacts | – |
| Current consumption K-bus | typ. 90 mA |
| Bit width in the process image | 2 outputs |
| Max. switching frequency | 6/min. (at rated load) |
| Operating cycles mech. (min.) | 5 x 106 |
| Operating cycles electr. (min.) | 1 x 106 (1В A/250В VВ AC) |
| Configuration | no address or configuration setting |
| Special features | reverse switching realizable |
| Weight | approx. 55 g |
| Operating/storage temperature | 0…+55°C/-25…+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/variable |
| Pluggable wiring | for all KSxxxx Bus Terminals |
| Approvals/markings | CE, UL |