| Number of outputs | 2 |
| Power supply | via the E-bus |
| Signal voltage | -10…+10 V |
| Oversampling factor | n = 1…100 selectable |
| Distributed clocks | yes |
| Distributed clock precision | |
| Load | > 5 kО© (short-circuit proof) |
| Resolution | 16 bit (incl. sign) |
| Output error | |
| Electrical isolation | 500 V (E-bus/signal voltage) |
| Conversion time | ~ 10 Вµs |
| Output rate | max. 100 ksamples/s |
| Current consumption power contacts | – |
| Current consumption E-bus | typ. 180 mA |
| Bit width in the process image | n x 2 x 16 bit output, 32 bit CycleCounter |
| Special features | oversampling |
| Weight | approx. 50 g |
| Operating/storage temperature | -25…+60°C/-40…+85°C |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| Protect. rating/installation pos. | IP20/variable |
| Pluggable wiring | for all ESxxxx terminals |
| Approvals/markings | CE, UL, ATEX, IECEx, cFMus |
| Ex marking | ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc cFMus: Class I, Division 2, Groups A, B, C, D Class I, Zone 2, AEx ec IIC T4 Gc |