| Number of inputs | 2 |
| Power supply | via the E-bus |
| Distributed clocks | – |
| Feed voltage potentiometer | – |
| Internal resistance | > 100 MО© |
| Input filter limit frequency | 100 Hz |
| Wiring fail indication | yes |
| Conversion time | typ. 10…400 ms, dependent on measuring range and settings |
| Measuring range | 100 mО©, 1 О©, 10 О©, 100 О©, 1 kО©, 10 kО©, 100 kО©, 1 MО©, 10 MО© |
| Range switching | automatic or through control |
| Resolution | 24 bit |
| Measurement error/uncertainty | |
| Electrical isolation | 1500 V (E-bus/field potential) |
| Current consumption power contacts | – |
| Current consumption E-bus | typ. 220 mA |
| Configuration | via the controller |
| Special features | automatic range selection, pulse and continuous measurement |
| Operating/storage temperature | 0…+55°C/-25…+85°C |
| Weight | approx. 55 g |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Approvals/markings | CE, UL, ATEX, IECEx |
| Protect. rating/installation pos. | IP20/variable |
| Ex marking | ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc |