Каталог

Technical dataEL3692
Number of inputs 2
Power supply via the E-bus
Distributed clocks –
Feed voltage potentiometer –
Internal resistance > 100 MО©
Input filter limit frequency 100 Hz
Wiring fail indication yes
Conversion time typ. 10…400 ms, dependent on measuring range and settings
Measuring range 100 mО©, 1 О©, 10 О©, 100 О©, 1 kО©, 10 kО©, 100 kО©, 1 MО©, 10 MО©
Range switching automatic or through control
Resolution 24 bit
Measurement error/uncertainty
Electrical isolation 1500 V (E-bus/field potential)
Current consumption power contacts –
Current consumption E-bus typ. 220 mA
Configuration via the controller
Special features automatic range selection, pulse and continuous measurement
Operating/storage temperature 0…+55°C/-25…+85°C
Weight approx. 55 g
Relative humidity 95%, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Approvals/markings CE, UL, ATEX, IECEx
Protect. rating/installation pos. IP20/variable
Ex marking ATEX:
II 3 G Ex ec IIC T4 Gc
IECEx:
Ex ec IIC T4 Gc