Каталог

Technical dataEL3403-0333
Number of inputs 3 x current, 3 x voltage
Wiring 2-wire
Ground reference (input) single-ended
Oversampling factor –
Distributed clocks –
Conversion time mains-synchronous
Measured values current, voltage, effective power, energy, cos П†, peak values U, I and P, frequency
Measuring voltage max. 500 V AC 3~ (ULX-N: max. 288 V AC)
Measuring current max. 1 A (AC), via measuring transformers xВ A/1В A
Resolution 1 ОјA, 0.1 mV, 10 mW
Measurement error/uncertainty 0.5% relative to full scale value (U/I), 1% calculated value
Measuring procedure true RMS
Update time net-synchronous
Electrical isolation 1500 V (E-bus/field potential)
Current consumption power contacts –
Current consumption E-bus typ. 120 mA
Bit width in the process image 62 byte PM input, 3 byte PM output
Special features true RMS value calculation, optional single-phase operation
Operating/storage temperature 0…+55°C/-25…+85°C
Weight approx. 75 g
Relative humidity 95%, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Pluggable wiring for all ESxxxx terminals
Approvals/markings CE, UL
Protect. rating/installation pos. IP20/variable