| Number of inputs | 2 x Pt100, 2 x -10…+10 V |
| Power supply | via the E-bus |
| Signal voltage | -10/0…+10 V |
| Distributed clocks | – |
| Internal resistance | > 130 kО© |
| Input filter limit frequency | typ. 1 kHz |
| Dielectric strength | max. 30 V |
| Sensor types | Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, resistance measurement (e.g. potentiometer, 10 Ω…1/4 kΩ), KTY sensors (types see documentation) |
| Connection method | 2-wire |
| Conversion time | RTD measurement: 85 ms default setting, 2…800 ms configurable, voltage measurement: 0.625 ms default setting, configurable, multiplex |
| Measuring current | |
| Temperature range | -200…+850°C (Pt sensors), -60…+250°C (Ni sensors) |
| Resolution | RTD measurement: 0.1В°C or 0.01В°C per digit, voltage measurement: 12 bit (16 bit presentation, incl. sign) |
| Measurement error/uncertainty | RTD measurement: |
| Electrical isolation | 500 V (E-bus/signal voltage) |
| Current consumption power contacts | – |
| Current consumption E-bus | typ. 130 mA |
| Special features | integrated digital filter, limit value monitoring |
| Operating/storage temperature | 0…+55°C/-25…+85°C |
| Weight | approx. 60 g |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Pluggable wiring | for all ESxxxx terminals |
| Approvals/markings | CE |
| Protect. rating/installation pos. | IP20/variable |