Technical dataEL3204-0162
Number of inputs 2 x Pt100, 2 x -10…+10 V
Power supply via the E-bus
Signal voltage -10/0…+10 V
Distributed clocks –
Internal resistance > 130 kО©
Input filter limit frequency typ. 1 kHz
Dielectric strength max. 30 V
Sensor types Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, resistance measurement (e.g. potentiometer, 10 Ω…1/4 kΩ), KTY sensors (types see documentation)
Connection method 2-wire
Conversion time RTD measurement: 85 ms default setting, 2…800 ms configurable, voltage measurement: 0.625 ms default setting, configurable, multiplex
Measuring current
Temperature range -200…+850°C (Pt sensors), -60…+250°C (Ni sensors)
Resolution RTD measurement: 0.1В°C or 0.01В°C per digit, voltage measurement: 12 bit (16 bit presentation, incl. sign)
Measurement error/uncertainty RTD measurement:
Electrical isolation 500 V (E-bus/signal voltage)
Current consumption power contacts –
Current consumption E-bus typ. 130 mA
Special features integrated digital filter, limit value monitoring
Operating/storage temperature 0…+55°C/-25…+85°C
Weight approx. 60 g
Relative humidity 95%, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Pluggable wiring for all ESxxxx terminals
Approvals/markings CE
Protect. rating/installation pos. IP20/variable