| Number of inputs | 1 |
| Power supply | via the E-bus |
| Distributed clocks | – |
| Input filter limit frequency | typ. 1 kHz |
| Sensor types | Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, resistance measurement (e.g. potentiometer, 10 Ω…1/4 kΩ), KTY sensors (types see documentation) |
| Connection method | 2-, 3-, 4-wire (default: 2-wire) |
| Conversion time | approx. 24 ms default setting, 4…500 ms configurable |
| Measuring current | |
| Temperature range | -200…+850°C (Pt sensors), -60…+250°C (Ni sensors) |
| Resolution | 0.1В°C per digit |
| Measurement error/uncertainty | |
| Electrical isolation | 500 V (E-bus/signal voltage) |
| Current consumption power contacts | – |
| Current consumption E-bus | typ. 190 mA |
| Bit width in the process image | 1 x 32 bit RTD input |
| Special features | integrated digital filter, limit value monitoring, variable connection technology |
| Operating/storage temperature | -25…+60°C/-40…+85°C |
| Weight | approx. 60 g |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Pluggable wiring | for all ESxxxx terminals |
| Approvals/markings | CE, UL, ATEX, IECEx |
| Protect. rating/installation pos. | IP20/variable |
| Ex marking | ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc |