Каталог

Technical dataEL3174-0030
Number of inputs 4
Ground reference (input) voltage: differential, current: single-ended
Power supply via the E-bus
Oversampling factor –
Distributed clocks yes
Distributed clock precision
Internal resistance > 200 kО© | typ. 85 О©
Input filter limit frequency 5 kHz
Common-mode voltage UCM max. 35 V (voltage measurement)
Dielectric strength max. 30 V (current measurement)
Conversion time minimum 150 Вµs
Measuring range, nominal -10/0…+10 V | -20/0/+4…+20 mA
Measuring range, technical -10.73…+10.73 V | -21.47…+21.47 mA
Resolution 16 bit (incl. sign)
Measurement error/uncertainty
Calibration certificate (analog) externally calibrated
Electrical isolation 500 V (E-bus/signal voltage)
Current consumption power contacts load-dependent
Current consumption E-bus typ. 180 mA
Bit width in the process image inputs: 16 byte
Configuration no address or configuration setting
Special features U/I parameterizable, ExtendedRange, standard and compact process image, activatable FIR/IIR filters
Operating/storage temperature 0…+55°C/-25…+85°C
Weight approx. 65В g
Relative humidity 95%, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Approvals/markings CE, UL
Protect. rating/installation pos. IP20/variable