Каталог

Technical dataEJ3314-0090
Number of inputs 4
Power supply via the E-bus
Distributed clocks –
Input filter limit frequency typ. 1 kHz
Conversion time approx. 2.5 s up to 20 ms, depending on configuration and filter setting, default: approx. 250 ms
Voltage measurement В±30/В±60/В±75В mV
Resolution 16 bit, representation adjustable: 0.1/0.01В°C or 1/2/4 ВµV per digit
Temperature measurement (thermocouple) type B, C, E, J, K, L, N, R, S, T, U (default setting: typeВ K)
Measurement uncertainty (temperature measurement) at 23В В°C ambient temperature with reference configuration, according type:
B: В±8.5В°C, C: В±6.2В°C, E: В±2.5В°C, J: В±2.7В°C, K: В±3В°C, L: В±2.3В°C, N: В±3В°C, R: В±6.7В°C, S: В±7.1В°C, T: В±2.9В°C, U: В±2.5В°C,
for further details see documentation

Measurement uncertainty (voltage measurement) at В±75В mV, 23В°C ambient temperature:
Electrical isolation 500 V (E-bus/field potential)
Special features channel by channel wire break detection, internal and external cold junction, firmware filter adjustable, TwinSAFE SC
Weight approx. 30 g
Operating/storage temperature 0…+55°C/-25…+85°C
Relative humidity 95%, no condensation
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
Protect. rating/installation pos. IP20/see documentation
Approvals/markings CE