| Number of inputs | 8 |
| Power supply | via the K-bus |
| Technology | 1-wire |
| Sensor types | Pt1000, Ni1000 |
| Measuring range | -50…+150°C (Pt sensors), -50…+150°C (Ni sensors) |
| Connection method | 1-wire |
| Conversion time | ~ 1 s |
| Measuring current | typ. ~ 0.5 mA |
| Resolution | 0.1В°C per digit |
| Measurement error/uncertainty | ~ В±1В°C, depending on wiring |
| Electrical isolation | 500 V (K-bus/signal voltage) |
| Current consumption power contacts | – |
| Current consumption K-bus | typ. 85 mA |
| Bit width in the process image | input: 8 x 16В bit data (8 x 8В bit control/status optional) |
| Configuration | no address setting, configuration via Bus Coupler or controller |
| Special features | open-circuit recognition |
| Weight | approx. 75 g |
| Operating/storage temperature | 0…+55°C/-25…+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/variable |
| Approvals/markings | CE, UL, ATEX, IECEx |
| Pluggable wiring | for all KSxxxx Bus Terminals |
| Ex marking | ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc |