| Number of inputs | 8 |
| Power supply | via the K-bus |
| Technology | 2-wire |
| Sensor types | Pt1000 (default), Ni1000, resistor/potentiometer 6/65/655 kО©, NTC 1.8 k/2.2 k/3 k/5 k/10 k/20 k/100 k |
| Measuring range | -50…+150°C (depending on sensor type) |
| Connection method | 2-wire |
| Conversion time | ~ 1 s |
| Measuring current | typ. |
| Resolution | 0.01В°C per digit |
| Measurement error/uncertainty | -20…+60°C: ±0.25°C at 25°C ambient temperature, -50…+150°C: ±1.5°C (for Pt/Ni sensors) |
| Electrical isolation | 500 V (K-bus/signal voltage) |
| Current consumption power contacts | – |
| Current consumption K-bus | typ. 85 mA |
| Bit width in the process image | input: 8 x 16В bit data (8 x 8В bit control/status optional) |
| Configuration | no address setting, configuration via Bus Coupler or controller |
| Special features | open-circuit recognition, cable resistance calibration, particularly suitable for building automation |
| Weight | approx. 75 g |
| Operating/storage temperature | -25…+60°C/-40…+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/variable |
| Approvals/markings | CE, UL, ATEX, IECEx |
| Ex marking | ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc |