| Number of inputs | 4 |
| Power supply | via the K-bus |
| Technology | 2-wire |
| Sensor types | Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, resistance measurement (e.g. potentiometer, 10 Ω…1.2/5 kΩ) |
| Measuring range | -200…+850°C (Pt sensors), -60…+250°C (Ni sensors) |
| Connection method | 2-wire |
| Conversion time | ~ 250 ms |
| Measuring current | typ. 0.5 mA |
| Resolution | 0.1В°C per digit |
| Measurement error/uncertainty | <> |
| Electrical isolation | 500 V (K-bus/signal voltage) |
| Current consumption power contacts | – (no power contacts) |
| Current consumption K-bus | typ. 60 mA |
| Bit width in the process image | input: 4 x 16 bit data (4 x 8 bit control/status optional) |
| Configuration | no address setting, configuration via Bus Coupler or controller |
| Special features | open-circuit recognition |
| Weight | approx. 70 g |
| Operating/storage temperature | -25…+60°C/-40…+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/variable |
| Approvals/markings | CE, UL, ATEX, IECEx, DNV GL |
| Pluggable wiring | for all KSxxxx Bus Terminals |
| Ex marking | ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc |