Каталог

Technical dataKL3142
Number of inputs 2
Power supply via the K-bus
Signal current 0…20 mA
Technology differential input
Internal resistance typ. 100 О© shunt
Common-mode voltage UCM max. В±10 V
Conversion time 140 ms, configurable
Filter 50 Hz, configurable
Resolution 16 bit
Measurement error/uncertainty
Surge voltage resistance 35 V DC
Electrical isolation 500 V (K-bus/signal voltage)
Current consumption power contacts –
Current consumption K-bus typ. 85 mA
Bit width in the process image input: 2 x 16В bit data (2 x 8В bit control/status optional)
Special features increased measuring accuracy
Weight approx. 70 g
Operating/storage temperature 0…+55°C/-25…+85°C
Relative humidity 95%, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos. IP20/variable
Approvals/markings CE, UL, ATEX, IECEx
Pluggable wiring for all KSxxxx Bus Terminals
Ex marking ATEX:
II 3 G Ex ec IIC T4 Gc
IECEx:
Ex ec IIC T4 Gc


+79043698209