| Number of inputs | 2 |
| Power supply | via the K-bus |
| Signal voltage | 0…10 V |
| Technology | single-ended |
| Internal resistance | typ. > 200 kО© |
| Common-mode voltage UCM | – |
| Conversion time | ~ 2 ms |
| Resolution | 12 bit |
| Measurement error/uncertainty | |
| Electrical isolation | 500 V (K-bus/signal voltage) |
| Current consumption power contacts | – (no power contacts) |
| Current consumption K-bus | typ. 60 mA |
| Bit width in the process image | input: 2 x 16В bit data (2 x 8В bit control/status optional) |
| Configuration | no address or configuration setting |
| Weight | approx. 60 g |
| Operating/storage temperature | 0…+55°C/-25…+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/variable |
| Approvals/markings | CE, UL, ATEX, IECEx |
| Pluggable wiring | for all KSxxxx Bus Terminals |
| Ex marking | ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc |