| Number of inputs | 4 |
| Signal current | 4…20 mA |
| Technology | single-ended |
| Internal resistance | 80В О© + diode voltage 0.7В V |
| Common-mode voltage UCM | – |
| Conversion time | ~ 4 ms |
| Resolution | 12 bit |
| Measurement error/uncertainty | |
| Surge voltage resistance | max. 35 V |
| Electrical isolation | 500 V (K-bus/signal voltage) |
| Current consumption power contacts | – (no power contacts) |
| Current consumption K-bus | typ. 75 mA |
| Bit width in the process image | input: 4 x 16 bit data (4 x 8 bit control/status optional) |
| Configuration | no address or configuration setting |
| Special features | for 2-wire sensors |
| Weight | approx. 70 g |
| Operating/storage temperature | -25…+60°C/-40…+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/variable |
| Approvals/markings | CE, UL, ATEX, IECEx, DNV GL, cFMus |
| Pluggable wiring | for all KSxxxx Bus Terminals |
| Ex marking | ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc cFMus: Class I, Division 2, Groups A, B, C, D Class I, Zone 2, AEx ec IIC T4 Gc |