| Connection technology | 4-wire |
| Number of outputs | 1 |
| Nominal voltage | 230 V AC (50 Hz) |
| Mains voltage | 230 V AC (50 Hz) |
| Rated output | 600 VA (W) |
| Rated current | max. 2.7 A |
| Load type | ohmic, inductive or capacitive (not mixed), lamp load, automatic load detection |
| Max. output current | 2.7 A |
| Short-circuit current | 20…40 A |
| Control type | phase control |
| Resolution | 1% |
| Electrical isolation | 500 V (K-bus/field voltage), 3750 V AC (1 min.) |
| Leakage current (OFF state) | |
| Current consumption power contacts | load only |
| Current consumption K-bus | typ. 95 mA |
| Bit width in the process image | output: 1 x 16В bit data (1 x 8В bit control/status optional) |
| Special features | dimmers with fieldbus functionality |
| Weight | approx. 60 g |
| Operating/storage temperature | 0…+55°C/-25…+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/see documentation |
| Pluggable wiring | for all KSxxxx Bus Terminals |
| Approvals/markings | CE |