Каталог

Technical dataKL1712
Connection technology 4-wire
Number of inputs 2
Nominal voltage 120 V AC/DC
“0” signal voltage 0…40 V
“1” signal voltage 80…140 V
Input filter typ. 10 ms
Input current > 3 mA, typ. 6 mA
Current consumption K-bus typ. 3 mA
Switching times 10 ms
Electrical isolation 500 V (K-bus/mains voltage), 3750 V AC, 1 min.
Bit width in the process image 2 inputs
Configuration no address or configuration setting
Special features 120 V AC power grids
Weight approx. 60 g
Operating/storage temperature 0…+55°C/-25…+85°C
Relative humidity 95%, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos. IP20/variable
Pluggable wiring for all KSxxxx Bus Terminals
Approvals/markings CE, UL, ATEX, IECEx
Ex marking ATEX:
II 3 G Ex ec IIC T4 Gc
IECEx:
Ex ec IIC T4 Gc