Каталог

Technical dataKL1501
Connection technology 1 x up/down counter, 2 x up or down counter
Specification EN 61131-2, type 1, “0”: 15 V DC, typ. 5 mA
Number of counters 1 or 2
Nominal voltage 24 V DC (-15%/+20%)
“0” signal voltage -3…+5 V (EN 61131-2, type 1)
“1” signal voltage 15…30 V (EN 61131-2, type 1)
Counting frequency max. 100 kHz (2 kHz for switching up/down)
Counter depth 32 bit
Input current typ. 5 mA (ENВ 61131-2, typeВ 1)
Max. output current 24 V/0.5 A (short-circuit proof) per channel
Current consumption K-bus typ. 50 mA
Current consumption power contacts load only
Electrical isolation 500 V (K-bus/field potential)
Bit width in the process image 40 inputs/outputs: 32 bit data, 8 bit control/status
Configuration no address setting, configuration via Bus Coupler or controller
Special features set counters, switch outputs
Weight approx. 50 g
Operating/storage temperature -25…+60°C/-40…+85°C
Relative humidity 95%, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos. IP20/variable
Pluggable wiring for all KSxxxx Bus Terminals
Approvals/markings CE, UL, ATEX, IECEx, cFMus
Ex marking ATEX:
II 3 G Ex ec IIC T4 Gc
IECEx:
Ex ec IIC T4 Gc
cFMus:
Class I, Division 2, Groups A, B, C, D
Class I, Zone 2, AEx ec IIC T4 Gc





+79043698209