| Number of channels | 8 inputs + 8 outputs |
| Input/output connections | M8, screw type |
| Input filter | 3.0 ms |
| “0” signal voltage | -3…+5 V |
| “1” signal voltage | 11…30 V, 6 mA input current (EN 61131-2, type 2) |
| Sensor supply | from control voltage, max. 0.5 A, short-circuit proof in total |
| Load type | ohmic, inductive, lamp load |
| Rated load voltage | 24 V DC (-15%/+20%) |
| Max. output current | 0.5 A per channel, individually short-circuit proof |
| Short-circuit current | typ. 1.5 A |
| Auxiliary power current | typ. 20 mA per channel |
| Current consumption from US (without sensor current) | see documentation |
| Power supply connection | feed: 1 x M8 male socket, 4-pin, a-coded, downstream connection: 1 x M8 female socket, 4-pin, a-coded |
| Bit width in the process image | 8 inputs + 8 outputs |
| Electrical isolation | channels/control voltage: no, between the channels: no, control voltage/fieldbus: depends on the bus system |