Каталог

Technical dataER3184-0002
Protocol EtherCAT
Bus interface 2 x M8 socket, 4-pin, a-coded, shielded
Number of inputs 4 (single-ended), 1 per socket
Input connections M12 x 1, 5-pin, a-coded
Conversion time ~ 100 Вµs
Resolution 16 bit (incl. sign)
Signal type -10/0…+10 V | 0/4…20 mA, parameterizable per channel
Common-mode voltage UCM max. 35 V
Internal resistance > 200 kО© | typ. 85 О© + diode voltage
Measurement error/uncertainty
Input filter limit frequency 5 kHz
Nominal voltage 24 V DC (-15%/+20%)
Distributed clocks yes
Input filter configurable
Sensor supply from load supply voltage UP
Current consumption from US 120 mA
Power supply connection feed: 1 x M8 male socket, 4-pin, a-coded, downstream connection: 1 x M8 female socket, 4-pin, a-coded
Electrical isolation 500 V
Special features current or voltage parameterizable
Weight approx. 265 g
Operating/storage temperature -25…+60°C/-40…+85°C
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos. IP65/66/67 (conforms to EN 60529)/variable
Approvals/markings CE, UL