Technical dataER1518-0002
Protocol EtherCAT
Bus interface 2 x M8 socket, 4-pin, a-coded, shielded
Specification EN 61131-2, type 1/3
Number of inputs 8, 2 of which can be used as 32 bit up/down counters
Input connections M12 x 1, 5-pin, a-coded
Counting frequency max. 1 kHz
Nominal input voltage 24 V DC (-15%/+20%)
Input filter adjustable 0…100 ms
“0” signal voltage -3…+5 V (EN 61131-2, type 3)
“1” signal voltage 11…30 V (EN 61131-2, type 3)
Input current typ. 3 mA (ENВ 61131-2, typeВ 3)
Distributed clocks yes
Power supply connection feed: 1 x M8 male socket, 4-pin, a-coded, downstream connection: 1 x M8 female socket, 4-pin, a-coded
Sensor supply from control voltage, max. 0.5 A per 4 sensors, short-circuit proof
Current consumption from US (without sensor current) 120 mA
Electrical isolation 500 V
Special features adjustable filters
Weight approx. 265 g
Operating/storage temperature -25…+60°C/-40…+85°C
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Approvals/markings CE, UL
Protect. rating/installation pos. IP65/66/67 (conforms to EN 60529)/variable