Technical dataEQ3204-0002
Protocol EtherCAT
Bus interface 2 x M8 socket, 4-pin, a-coded, shielded
Number of inputs 4
Input connections M12 x 1, 5-pin, a-coded
Connection method M12 socket for 2-, 3- and 4-wire connections, presetting: 2-wire
Conversion time 800 ms up to 2 ms, see documentation, default: approx. 85 ms
Resolution 0.1В°C per digit
Sensor types Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, resistance measurement (e.g. potentiometer, 10 Ω…1.2/4 kΩ)
Signal type Pt100
Measuring range -200…+850°C (Pt sensors), -60…+250°C (Ni sensors)
Measurement error/uncertainty
Nominal voltage 24 V DC (-15%/+20%)
Distributed clocks –
Measuring current typ. 0.5 mA
Input filter 5 variations, configurable
Current consumption from US 120 mA
Power supply connection feed: 1 x M8 male socket, 4-pin, a-coded, downstream connection: 1 x M8 female socket, 4-pin, a-coded
Electrical isolation 500 V
Special features stainless steel, Hygienic Design
Operating/storage temperature -25…+60°C/-40…+85°C
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos. IP69K (according to EN 60529)/variable
Approvals/markings CE, UL