Technical dataEPI2339-0022
Communication IO-Link
Interfaces 1 x M12 plug, A-coded
Data transfer rates 230.4 kbaud (COM 3)
Specification version IO-Link V1.1, Class B
Number of channels 16 digital inputs or outputs
Input/output connections M12, screw type
Input filter 3.0 ms (default), adjustable 0…20 ms
“0” signal voltage -3…+5 V (EN 61131-2, type 3)
“1” signal voltage 11…30 V (EN 61131-2, type 3)
Input current typ. 3 mA (ENВ 61131-2, typeВ 3)
Sensor supply from P24, max 0.5В A, short-circuit proof in total
Load type ohmic, inductive, lamp load
Rated load voltage 24 V DC (-15%/+20%)
Max. output current 0.5 A per channel, from P24, individually short-circuit proof, ∑ 4 A
Short-circuit current max. 1.5 A
Current consumption typ. 100 mA from L+
Auxiliary power current typ. 20 mA + load
Electrical isolation L+/P24: yes
Weight approx. 250 g
Operating/storage temperature -25…+60°C/-40…+85°C
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Approvals/markings CE, UL
Protect. rating/installation pos. IP65/66/67 (conforms to EN 60529)/variable