Каталог

Technical dataEP6228-3132
Protocol EtherCAT
Bus interface 2 x M8 socket, 4-pin, a-coded, shielded
Data transfer rates 4.8 kbaud, 38.4 kbaud and 230.4 kbaud
Connection method M12 socket, 5-pin, a-coded
Number of inputs 4 digital inputs
Nominal input voltage 24 V DC (-15%/+20%)
Input filter 10 Вµs
“0” signal voltage -3…+5 V
“1” signal voltage 11…30 V (EN 61131-2, type 3)
Input current typ. 3 mA (ENВ 61131-2, typeВ 3)
Specification version IO-Link V1.1, 4 x Class A, 4 x Class B
IO-Link interfaces 8
Nominal voltage 24 V DC (-15%/+20%)
Distributed clocks –
IO-Link sensor supply L+ 24 V DC, 1.4 A per port, ∑ 5.6 A
IO-Link extra power P24 24 V DC, max. 4.0 A per port, ∑ 4.0 A for 2 ports each for Class B
Current consumption from US typ. 130 mA + load
Power supply connection feed: 1 x 7/8′ plug, 5-pin, downstream connection: 1 x 7/8′ socket, 5-pin
Electrical isolation 500 V
Special features Class A ports: 1, 2, 5, 6, Class B ports: 3, 4, 7, 8
Weight approx. 440 g
Operating/storage temperature -25…+60°C/-40…+85°C
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos. IP65/66/67 (conforms to EN 60529)/variable
Approvals/markings CE, UL (in preparation)
+79043698209