Technical dataEP2624-0002
Protocol EtherCAT
Bus interface 2 x M8 socket, 4-pin, a-coded, shielded
Number of outputs 4 x make contacts
Ohmic switching current 0.5 A AC/2 A DC per channel
Output connections M12 x 1, 5-pin, a-coded
Minimum permitted load 10 ВµA at 10 mV DC
Load type ohmic, inductive, lamp load
Nominal output voltage 25 V AC/30 V DC
Distributed clocks –
Current consumption from US 200В mA
Power supply connection feed: 1 x M8 male socket, 4-pin, a-coded, downstream connection: 1 x M8 female socket, 4-pin, a-coded
Operating cycles mech. (min.) 1 x 108
Operating cycles electr. (min.) 2 x 105 (1В A/30В VВ DC)
Electrical isolation 500 V
Special features potential-free switching
Weight approx. 165 g
Operating/storage temperature -25…+60°C/-40…+85°C
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos. IP65/66/67 (conforms to EN 60529)/variable
Approvals/markings CE, UL, ATEX
Ex marking II 3 G Ex nA IIC T4 Gc