| Technology | current input |
| Signal current | 4…20 mA |
| Number of inputs | 1 (single-ended) |
| Connection method | 2-wire |
| Resolution | 16 bit (incl. sign) |
| Measurement error/uncertainty | |
| Internal resistance | typ. 250 О© |
| Input filter limit frequency | 25 Hz |
| Conversion time | typ. 1 ms |
| Supply voltage electronics | 24 V DC (via power contacts), ELX9560 power supply |
| Current consumption power contacts | typ. 15 mA + load |
| Current consumption E-bus | typ. 85 mA |
| Distributed clocks | yes |
| Special features | standard and compact process image, activatable FIR/IIR filters, limit value monitoring, NE43В NAMUR |
| Weight | approx. 60 g |
| Operating/storage temperature | -25…+60°C/-40…+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/see documentation |
| Approvals/markings | CE, UL, ATEX, IECEx, cFMus, CCC |
| Ex marking | ATEX: В В II 3(1)G Ex ec [ia Ga] IIC T4 Gc В В II (1)D [Ex ia Da] IIIC В В I (M1) [Ex ia Ma] I IECEx: В В Ex ec [ia Ga] IIC T4 Gc В В [Ex ia Da] IIIC В В [Ex ia Ma] I cFMus: В В AIS Class I, II, III, Division 1, Groups A thru G В В Class I, Division 2, Groups A, B, C, D В Class I, Zone 2, AEx ec [ia Ga] IIC T4 Gc В В [AEx ia Da] IIIC T4 |