| Connection technology | terminal contact |
| Data transfer channels | TxD and RxD, full/half duplex |
| Data transfer rates | 2400…115,200 baud, default: 9600 baud, 8 data bits, no parity and one stop bit |
| Interfaces | 1 x RS422/RS485 |
| Bit transfer | with differential signal |
| Line impedance | 120 О© |
| Cable length | approx. 1000 m twisted pair |
| Providing external supply | – |
| Power supply | via the E-bus |
| Distributed clocks | – |
| Electrical isolation | 500 V (E-bus/signal voltage) |
| Data buffer | 864В bytes receive buffer, 128В bytes transmit buffer |
| Configuration | no address setting, configuration via PLC |
| Current consumption power contacts | – |
| Current consumption E-bus | typ. 170 mA |
| Weight | approx. 55 g |
| Operating/storage temperature | -25…+60°C/-40…+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/variable |
| Pluggable wiring | for all ESxxxx terminals |
| Approvals/markings | CE, UL, ATEX, IECEx, cFMus |
| Ex marking | ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc cFMus: Class I, Division 2, Groups A, B, C, D Class I, Zone 2, AEx ec IIC T4 Gc |