Каталог

Technical dataEL3356-0090
Number of inputs 2, for 1 resistor bridge in full bridge technology
Power supply via the E-bus
Distributed clocks yes
Measuring range UD max. В±27 mV
Measuring range UREF max. В±13.8 V
Internal resistance > 200 kО© (UREF), > 1 MО© (UD)
Supported nominal sensitivity all, parameter resolution: 0.01 µV/V, recommended: 0.5…4 mV/V
Input filter limit frequency 10 kHz low pass (-3 dB)
Conversion rate 10,000…4 samples/s (0.1…250 ms conversion time)
Power supply UV up to 12 V DC from power contacts, dependent on sensor
Resolution 24 bit, 32 bit presentation
Measurement error/uncertainty
Current consumption power contacts depends on strain gauge supply, min. 1 mA
Current consumption E-bus typ. 280 mA
Special features TwinSAFE SC, self-calibration, quadruple averager, dynamic filters
Operating/storage temperature 0…+55°C/-25…+85°C
Weight approx. 60 g
Relative humidity 95%, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Pluggable wiring for all ESxxxx terminals
Approvals/markings CE, UL, ATEX, IECEx
Protect. rating/installation pos. IP20/variable
Ex marking ATEX:
II 3 G Ex ec IIC T4 Gc
IECEx:
Ex ec IIC T4 Gc


+79043698209