| Number of inputs | 2, for 1 resistor bridge in full bridge technology |
| Distributed clocks | yes |
| Measuring range UD | max. -25…+25 mV rated voltage |
| Measuring range UREF | max. -12…+12 V rated voltage |
| Internal resistance | > 200 kО© (UREF), > 1 MО© (UD) |
| Supported nominal sensitivity | all, parameter resolution: 0.01 µV/V, recommended: 0.5…4 mV/V |
| Input filter limit frequency | 10 kHz low pass (-3 dB) |
| Conversion time | 0.1…250 ms, configurable, max. 10,000 samples/s |
| Conversion rate | 10,000…4 samples/s (0.1…250 ms conversion time) |
| Power supply UV | up to 12 V DC from power contacts, dependent on sensor |
| Resolution | 24 bit, 32 bit presentation |
| Measurement error/uncertainty | |
| Calibration certificate (analog) | factory calibrated |
| Current consumption power contacts | depends on strain gauge supply, min. 1 mA |
| Current consumption E-bus | typ. 280 mA |
| Special features | self-calibration, quadruple averager, dynamic filters, fast data sampling, with calibration certificate |
| Operating/storage temperature | 0…+55°C/-25…+85°C |
| Weight | approx. 60 g |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Approvals/markings | CE, UL, ATEX, IECEx |
| Protect. rating/installation pos. | IP20/variable |
| Ex marking | ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc |