Каталог

Technical dataEL3318
Number of inputs 8
Power supply via the E-bus
Distributed clocks –
Input filter limit frequency typ. 1 kHz
Connection method 2-wire
Conversion time approx. 2.5 s up to 20 ms, depending on configuration and filter setting, default: approx. 250 ms
Voltage measurement В±30/В±60/В±75В mV
Resolution 16 bit, representation adjustable: 0.1/0.01В°C or 1/2/4 ВµV per digit
Temperature measurement (thermocouple) type B, C, E, J, K, L, N, R, S, T, U (default setting: typeВ K)
Measurement uncertainty (temperature measurement) at 23В В°C ambient temperature, with internal cold junction, according type:
B: В±6.3В°C, C: В±4.9В°C, E: В±3.1В°C, J: В±3.2В°C, K: В±3.0В°C, L: В±3.1В°C, N: В±3.4В°C, R: В±5.2В°C, S: В±5.4В°C, T: В±3.3В°C, U: В±3.2В°C,
for further details see documentation

Measurement uncertainty (voltage measurement) at В±75В mV, 23В°C ambient temperature:
Electrical isolation 500 V (E-bus/signal voltage)
Current consumption power contacts –
Current consumption E-bus typ. 210 mA
Special features channel by channel wire break detection, internal and external cold junction, firmware filter adjustable
Operating/storage temperature -25…+60°C/-40…+85°C
Weight approx. 70 g
Relative humidity 95%, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Approvals/markings CE, UL, ATEX, IECEx, cFMus
Protect. rating/installation pos. IP20/variable
Ex marking ATEX:
В В II 3G Ex ec IIC T4 Gc
IECEx:
В В Ex ec IIC T4 Gc
cFMus:
В В Class I, Division 2, Groups A, B, C, D
В В Class I, Zone 2, AEx ec IIC T4 Gc