| Number of inputs | 8 |
| Power supply | via the E-bus |
| Distributed clocks | – |
| Input filter limit frequency | typ. 1 kHz |
| Connection method | 2-wire |
| Conversion time | approx. 2.5 s up to 20 ms, depending on configuration and filter setting, default: approx. 250 ms |
| Voltage measurement | В±30/В±60/В±75В mV |
| Resolution | 16 bit, representation adjustable: 0.1/0.01В°C or 1/2/4 ВµV per digit |
| Temperature measurement (thermocouple) | type B, C, E, J, K, L, N, R, S, T, U (default setting: typeВ K) |
| Measurement uncertainty (temperature measurement) | at 23В В°C ambient temperature, with internal cold junction, according type: B: В±6.3В°C, C: В±4.9В°C, E: В±3.1В°C, J: В±3.2В°C, K: В±3.0В°C, L: В±3.1В°C, N: В±3.4В°C, R: В±5.2В°C, S: В±5.4В°C, T: В±3.3В°C, U: В±3.2В°C, for further details see documentation |
| Measurement uncertainty (voltage measurement) | at В±75В mV, 23В°C ambient temperature: |
| Electrical isolation | 500 V (E-bus/signal voltage) |
| Current consumption power contacts | – |
| Current consumption E-bus | typ. 210 mA |
| Special features | channel by channel wire break detection, internal and external cold junction, firmware filter adjustable |
| Operating/storage temperature | -25…+60°C/-40…+85°C |
| Weight | approx. 70 g |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Approvals/markings | CE, UL, ATEX, IECEx, cFMus |
| Protect. rating/installation pos. | IP20/variable |
| Ex marking | ATEX: В В II 3G Ex ec IIC T4 Gc IECEx: В В Ex ec IIC T4 Gc cFMus: В В Class I, Division 2, Groups A, B, C, D В В Class I, Zone 2, AEx ec IIC T4 Gc |