| Number of inputs | 4 |
| Power supply | via the E-bus |
| Oversampling factor | – |
| Distributed clocks | yes |
| Distributed clock precision | |
| Internal resistance | > 200 kО© | typ. 85 О© |
| Input filter limit frequency | 5 kHz |
| Conversion time | minimum 150 Вµs |
| Measuring range, nominal | -3…+3 V | -20/0/+4…+20 mA |
| Measuring range, technical | -3.22…+3.22 V | -21.47…+21.47 mA |
| Resolution | 16 bit (incl. sign) |
| Measurement error/uncertainty | |
| Electrical isolation | 2500 V functional isolation (test voltage channel/channel and channel/fieldbus, production test) |
| Current consumption power contacts | – |
| Current consumption E-bus | typ. 150 mA |
| Bit width in the process image | inputs: 16 byte |
| Configuration | no address or configuration setting |
| Special features | U/I parameterizable, ExtendedRange, standard and compact process image, activatable FIR/IIR filters |
| Operating/storage temperature | -25…+60°C/-40…+85°C |
| Weight | approx. 65В g |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Approvals/markings | CE, ATEX, IECEx, cFMus |
| Protect. rating/installation pos. | IP20/variable |
| Ex marking | ATEX: В В II 3G Ex ec IIC T4 Gc IECEx: В В Ex ec IIC T4 Gc cFMus: В В Class I, Division 2, Groups A, B, C, D В В Class I, Zone 2, AEx ec IIC T4 Gc |