Technical dataEL3001
Number of inputs 1 (single-ended)
Power supply via the E-bus
Signal voltage -10…+10 V
Distributed clocks –
Internal resistance > 130 kО©
Input filter limit frequency 1 kHz
Dielectric strength max. 30 V
Conversion time 0.625 ms default setting, configurable, multiplex
Resolution 12 bit (16 bit presentation incl. sign)
Measurement error/uncertainty
Electrical isolation 500 V (E-bus/field potential)
Current consumption power contacts –
Current consumption E-bus typ. 130 mA
Bit width in the process image inputs: 4 byte
Configuration no address or configuration setting required
Special features standard and compact process image, switchable measuring data representation, activatable FIR/IIR filters, limit value monitoring, overload display in the process data
Operating/storage temperature -25…+60°C/-40…+85°C
Weight approx. 70 g
Relative humidity 95%, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Pluggable wiring for all ESxxxx terminals
Approvals/markings CE, UL, ATEX, IECEx
Protect. rating/installation pos. IP20/variable
Ex marking ATEX:
II 3 G Ex ec IIC T4 Gc
IECEx:
Ex ec IIC T4 Gc