Каталог

Technical dataEL2634
Connection technology relay output
Number of outputs 4 x make contacts
Nominal voltage 250 V AC/30 V DC
Load type ohmic, inductive
Distributed clocks –
Ohmic switching current 4В AВ AC/DC per channel
Minimum permitted load 0.1В mA at 0.1В VВ DC (at 120 operations/min.)
Inductive switching current 2 A AC/DC per channel
Lamp test, electronic ballast –
Current consumption E-bus 80 mA
Electrical isolation 500 V (E-bus/field potential)
Current consumption power contacts –
Bit width in the process image 4 outputs
Operating cycles mech. (min.) 2 x 107 (at 18 x 103 switching cycles per hour)
Operating cycles electr. (min.) 1 x 105 (3В A/30В VВ DC ohmic load)
Configuration no address or configuration setting
Weight approx. 70 g
Operating/storage temperature -25…+60°C/-40…+85°C
Relative humidity 95%, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Pluggable wiring for all ESxxxx terminals
Approvals/markings CE, UL
+79043698209