Technical dataEL2622-0010
Connection technology relay output
Number of outputs 2 x make contacts
Nominal voltage 230 V AC/30 V DC
Load type ohmic, inductive, capacitive
Distributed clocks –
Switching current 5 A AC/DC per channel
Minimum permitted load 0.1 mA at 0.1 V DC
Inductive switching current 2 A AC/DC per channel
Current consumption E-bus typ. 120 mA
Electrical isolation 500 V (E-bus/field potential)
Current consumption power contacts –
Bit width in the process image 2 outputs + 1 input
Operating cycles mech. (min.) 2 x 107
Operating cycles electr. (min.) 8 x 104 (5В A/30В VВ DC or 5 A/250 VВ AC and ohmic load)
Configuration no address or configuration setting
Special features soft switching at zero voltage crossing significantly extends service life with AC voltage supply
Weight approx. 50 g
Operating/storage temperature 0…+55°C/-25…+85°C
Relative humidity 95%, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos. IP20/variable
Pluggable wiring for all ESxxxx terminals
Approvals/markings CE, UL