Technical dataEL2034
Connection technology 2-wire
Number of outputs 4
Nominal voltage 24 V DC (-15%/+20%)
Load type ohmic, inductive, lamp load
Distributed clocks –
Max. output current 2.0 A (short-circuit proof) per channel, with diagnostics
Short-circuit current typ.
Reverse voltage protection yes
Breaking energy
Switching times typ. TON: 40 Вµs, typ. TOFF: 200 Вµs
Current consumption E-bus typ. 120 mA
Electrical isolation 500 V (E-bus/field potential)
Current consumption power contacts typ. 14 mA + load
Bit width in the process image 4 outputs + 4 diagnostic inputs
Configuration no address or configuration setting
Special features diagnostics: short circuit and open circuit
Weight approx. 55 g
Operating/storage temperature -25…+60°C/-40…+85°C
Relative humidity 95%, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos. IP20/variable
Pluggable wiring for all ESxxxx terminals
Approvals/markings CE, UL, ATEX, IECEx
Ex marking ATEX:
II 3 G Ex ec IIC T4 Gc
IECEx:
Ex ec IIC T4 Gc


+79043698209