Каталог

Technical dataEL2014
Connection technology 2-wire
Number of outputs 4
Nominal voltage 24 V DC (-15%/+20%)
Load type ohmic, inductive, lamp load
Distributed clocks –
Max. output current 0.5 A (short-circuit proof) per channel
Short-circuit current typ.
Reverse voltage protection yes
Breaking energy
Switching times typ. TON: 50 Вµs, typ. TOFF: 100 Вµs
Current consumption E-bus typ. 60 mA
Electrical isolation 500 V (E-bus/field potential)
Current consumption power contacts typ. 15 mA + load
Bit width in the process image 4 bit output, 20 bit diagnositcs
Configuration via TwinCAT System Manager
Special features diagnostics via process data and LED: overtemperature, PowerFail, short circuit (per channel)
Weight approx. 70 g
Operating/storage temperature 0…+55°C/-25…+85°C
Relative humidity 95%, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos. IP20/variable
Pluggable wiring for all ESxxxx terminals
Approvals/markings CE, ATEX, IECEx, cFMus
Ex marking ATEX:
II 3 G Ex ec IIC T4 Gc
IECEx:
Ex ec IIC T4 Gc
cFMus:
Class I, Division 2, Groups A, B, C, D
Class I, Zone 2, AEx ec IIC T4 Gc





+79043698209