Technical dataEL1024
Connection technology 2-wire
Specification EN 61131-2, type 2
Number of inputs 4
Nominal voltage 24 V DC (-15%/+20%)
“0” signal voltage -3…+5 V (EN 61131-2, type 2)
“1” signal voltage 11…30 V (EN 61131-2, type 2)
Input current typ. 6 mA (EN 61131-2, type 2)
Input filter typ. 3.0 ms
Distributed clocks –
Current consumption power contacts typ. 30 mA + load
Current consumption E-bus typ. 90 mA
Electrical isolation 500 V (E-bus/field potential)
Configuration no address or configuration setting
Special features type 2
Weight approx. 50 g
Operating/storage temperature 0…+55°C/-25…+85°C
Relative humidity 95%, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos. IP20/variable
Pluggable wiring for all ESxxxx terminals
Approvals/markings CE, UL, ATEX, IECEx
Ex marking ATEX:
II 3 G Ex ec IIC T4 Gc
IECEx:
Ex ec IIC T4 Gc