Каталог

Technical dataEJ2502
Power supply via the E-bus
Number of outputs 2
Rated load voltage 24 V DC (-15%/+20%)
Load type ohmic, inductive, lamp load
Distributed clocks –
Max. output current 0.5 A (short-circuit proof) per channel
Short-circuit current typ.
Base frequency 1…20 kHz, 250 Hz default
Duty factor 0…100%
Resolution 9…15 bit
Reverse voltage protection yes
Switching times TON: > 750 ns, TOFF: > 500 ns
Auxiliary power current typ. 10 mA + load
Current consumption E-bus typ. 110 mA
Electrical isolation 500 V (E-bus/field potential)
Special features separate frequency can be set for each channel
Weight approx. 30 g
Operating/storage temperature -25…+60°C/-40…+85°C
Relative humidity 95%, no condensation
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
Protect. rating/installation pos. IP20/see documentation
Approvals/markings CE, UL