| Power supply | via the E-bus |
| Number of outputs | 2 |
| Rated load voltage | 24 V DC (-15%/+20%) |
| Load type | ohmic, inductive, lamp load |
| Distributed clocks | – |
| Max. output current | 0.5 A (short-circuit proof) per channel |
| Short-circuit current | typ. |
| Base frequency | 1…20 kHz, 250 Hz default |
| Duty factor | 0…100% |
| Resolution | 9…15 bit |
| Reverse voltage protection | yes |
| Switching times | TON: > 750 ns, TOFF: > 500 ns |
| Auxiliary power current | typ. 10 mA + load |
| Current consumption E-bus | typ. 110 mA |
| Electrical isolation | 500 V (E-bus/field potential) |
| Special features | separate frequency can be set for each channel |
| Weight | approx. 30 g |
| Operating/storage temperature | -25…+60°C/-40…+85°C |
| Relative humidity | 95%, no condensation |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| Protect. rating/installation pos. | IP20/see documentation |
| Approvals/markings | CE, UL |