| Number of inputs | 2, for 1 resistor bridge |
| Power supply | via the K-bus |
| Signal voltage | UD: -20…+20 mV UREF: -12…+12 V |
| Signal voltage UD, UREF | -20…+20 mV, -12…+12 V |
| Technology | strain gauge connection |
| Internal resistance | > 200 kО© (UREF), > 1 MО© (UD) |
| Power supply UV | via power contacts |
| Conversion time | |
| Filter | 50 Hz, configurable |
| Resolution | 16 bit |
| Measurement error/uncertainty | |
| Current consumption power contacts | load only |
| Current consumption K-bus | typ. 85 mA |
| Bit width in the process image | input: 2 x 16В bit data (2 x 8В bit control/status optional) |
| Special features | increased measuring accuracy, self-calibration |
| Weight | approx. 75 g |
| Operating/storage temperature | 0…+55°C/-25…+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/variable |
| Approvals/markings | CE, UL, ATEX, IECEx |
| Pluggable wiring | for all KSxxxx Bus Terminals |
| Ex marking | ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc |