| Protocol | EtherCAT |
| Bus interface | 2 x M8 socket, 4-pin, a-coded, shielded |
| Specification | NAMUR (IEC 60947-5-6) |
| Number of inputs | 8 |
| Input connections | M12 x 1, 5-pin, a-coded |
| Connection method | 2-wire |
| Open circuit voltage | typ. 8.2 V DC |
| “0” signal current | ≤ 1.2 mA |
| “1” signal current | ≥ 2.1 mA |
| Switching hysteresis | typ. 300 ВµA |
| Short-circuit current | typ. 7 mA |
| Fault detection | I ≤ 200 µA (cable break), I ≥ 6.3 mA (short circuit) |
| Max. switching frequency | 1В kHz |
| Power supply connection | feed: 1 x M8 male socket, 4-pin, a-coded, downstream connection: 1 x M8 female socket, 4-pin, a-coded |
| Sensor supply | from load supply voltage UP |
| Current consumption from US | 50 mA |
| Special features | can be parameterized by channel: NAMUR NO/NC, potential-free contacts NO/NC |
| Weight | approx. 250 g |
| Operating/storage temperature | -25…+70°C/-40…+85°C |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP65/66/67 (conforms to EN 60529)/variable |
| Approvals/markings | CE, UL, ATEX, IECEx |
| Ex marking | ATEX: II 3(1)G Ex ec [ia Ga] IIC T4 Gc II 3(1)D Ex tc [ia Da] IIIC T135 В°C Dc I (M1) [Ex ia Ma] I IECEx: Ex ec [ia Ga] IIC T4 Gc Ex tc [ia Da] IIIC T135 В°C Dc [Ex ia Ma] I |