| Protocol | EtherCAT |
| Bus interface | 2 x M8 socket, P-coded, shielded |
| Data transfer rates | 4.8 kbaud, 38.4 kbaud and 230.4 kbaud |
| Sensor supply | from load supply voltage, max. 0.5 A, short-circuit proof in total |
| Connection method | M12 socket, 5-pin, a-coded |
| Number of channels | 4 digital timestamp inputs, 8 digital inputs or outputs |
| Input filter | 10 Вµs |
| “0” signal voltage | -3…+5 V |
| “1” signal voltage | 11…30 V (EN 61131-2, type 3) |
| Max. output current | 0.5 A per channel, individually short-circuit proof |
| Specification version | IO-Link V1.1, Class A |
| IO-Link interfaces | 4 |
| Nominal voltage | 24 V DC (-15%/+20%) |
| Distributed clocks | yes |
| IO-Link sensor supply L+ | 24 V DC, 1.4 A per port, ∑ 3.0 A for 4 ports |
| Switching times | typ. TON: 60 Вµs, typ. TOFF: 300 Вµs |
| Current consumption from US | typ. 130 mA + load |
| Power supply connection | feed: 1 x M8 male socket, 4-pin, a-coded, downstream connection: 1 x M8 female socket, 4-pin, a-coded |
| Electrical isolation | 500 V |
| Special features | Timestamp inputs, 8 digital combi channels |
| Weight | approx. 250 g |
| Operating/storage temperature | -25…+60°C/-40…+85°C |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP65/66/67 (conforms to EN 60529)/variable |
| Approvals/markings | CE, UL (in preparation) |