Technical dataEP6001-0002
Protocol EtherCAT
Bus interface 2 x M8 socket, 4-pin, a-coded, shielded
Data transfer channels 1
Interfaces individually selectable from RS232, RS485, RS422
Data transfer rates 300…115,200 baud, 9600 baud (8 bit, no parity, 1 stop bit) is preset
Communication TxD and RxD, full duplex
Bit distortion <>
Cable length RS232: max. 15 m, RS422/RS485: approx. 1000 m
Data buffer 864В bytes receive buffer, 128В bytes transmit buffer
Sensor supply +5 V DC, 1 A
Connection method M12 socket, 5-pin, a-coded
Number of channels 2 digital inputs or outputs
Input filter 10 Вµs (for digital inputs)
“0” signal voltage -3…+5 V
“1” signal voltage 11…30 V
Input current typ. 3 mA (ENВ 61131-2, typeВ 3)
Load type ohmic, inductive, lamp load
Rated load voltage 24 V DC (-15%/+20%)
Max. output current 0.5 A per channel, individually short-circuit proof
Short-circuit current typ. 1.5 A
Nominal voltage 24 V DC (-15%/+20%)
Distributed clocks –
Current consumption from US typ. 130 mA + sensor supply
Power supply connection feed: 1 x M8 male socket, 4-pin, a-coded, downstream connection: 1 x M8 female socket, 4-pin, a-coded
Electrical isolation 500 V
Special features easy integration of serial end devices
Weight approx. 165 g
Operating/storage temperature -25…+60°C/-40…+85°C
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos. IP65/66/67 (conforms to EN 60529)/variable
Approvals/markings CE, UL