| Protocol | EtherCAT |
| Bus interface | 2 x M8 socket, 4-pin, a-coded, shielded |
| Number of inputs | 4 |
| Connection method | M12 socket, 2-wire connection for thermocouple |
| Conversion time | approx. 2.5 s up to 20 ms, depending on configuration and filter setting, see documentation, default: approx. 250 ms |
| Voltage measurement | В±30/В±60/В±75В mV |
| Resolution | 16 bit, representation adjustable: 0.1/0.01В°C or 1/2/4 ВµV per digit |
| Sensor types | types B, C, E, J, K, L, N, R, S, T, U (default setting type K), mV measurement |
| Measuring range | depending on sensor type, preset value is type K, -100…+1370°C |
| Measurement error/uncertainty | |
| Nominal voltage | 24 V DC (-15%/+20%) |
| Distributed clocks | – |
| Input filter | 5 variations, configurable |
| Sensor supply | – |
| Current consumption from US | 120 mA |
| Power supply connection | feed: 1 x M8 male socket, 4-pin, a-coded, downstream connection: 1 x M8 female socket, 4-pin, a-coded |
| Electrical isolation | 500 V |
| Special features | open-circuit recognition |
| Weight | approx. 165 g |
| Operating/storage temperature | -25…+60°C/-40…+85°C |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP65/66/67 (conforms to EN 60529)/variable |
| Approvals/markings | CE, UL, ATEX |
| Ex marking | II 3 G Ex nA IIC T4 Gc |