Technical dataEP3182-1002
Protocol EtherCAT
Bus interface 2 x M8 socket, 4-pin, a-coded, shielded
Number of inputs 2 (single-ended)
Number of outputs 2 (digital 24 V DC)
Connection method M12 socket, 5-pin, a-coded
Conversion time ~ 100 Вµs
Resolution 16 bit (incl. sign)
Signal type -10/0…+10 V | 0/4…20 mA, parameterizable per channel
Common-mode voltage UCM max. 35 V
Internal resistance > 200 kО© | typ. 85 О© + diode voltage
Measurement error/uncertainty
Input filter limit frequency 5 kHz
Nominal voltage 24 V DC (-15%/+20%)
Input filter configurable
Max. output current 2 mA (short-circuit proof) per channel
Sensor supply from load supply voltage UP
Current consumption from US 120 mA
Power supply connection feed: 1 x M8 male socket, 4-pin, a-coded, downstream connection: 1 x M8 female socket, 4-pin, a-coded
Electrical isolation control voltage/fieldbus: yes
Special features current or voltage parameterizable, 2 digital outputs (sink/source type)
Operating/storage temperature 0…+55°C/-25…+85°C
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos. IP65/66/67 (conforms to EN 60529)/variable
Approvals/markings CE, UL