Technical dataAnalog input
Function power measurement
Ground reference (input) single-ended
Max. sampling rate min. 500 Вµs (max. 2 ksps) per channel
Sampling type multiplex, approx. 60 Вµs delay between. Ch1/2
Internal resistance typ. 100 О©
Sensor supply from load supply voltage, max. 0.5 A, short-circuit proof in total
Input filter limit frequency 1.2 kHz
Rise time 3 ms typ. (0…90%)
Dielectric strength max. 30 V (voltage and current measurement)
Overcurrent protection typ.
Measuring range, nominal -20/0/+4…+20 mA
Measuring range, technical -21.47…+21.47 mA
Resolution 16 bit (incl. sign)
Measurement error/uncertainty
Electrical isolation channel/channel no