| Number of inputs | 1 |
| Power supply | via the E-bus |
| Oversampling factor | n = 1…64 |
| Distributed clocks | yes |
| Distributed clock precision | |
| Internal resistance | > 500 kО© (30 V), > 4 MО© (others), 150 О© (current) |
| Input filter limit frequency | 3 kHz |
| Dielectric strength | max. 36 V |
| Conversion time | 100 Вµs/10 ksps |
| Resolution | 24 bit (incl. sign) |
| Measurement error/uncertainty | typ. В±0.01% relative to the respective full scale value @ 23В°C in some measuring ranges, see documentation |
| Calibration certificate (analog) | factory calibrated |
| Electrical isolation | 500 V (E-bus/signal voltage) |
| Current consumption power contacts | – |
| Current consumption E-bus | typ. 260 mA |
| Configuration | no address or configuration setting |
| Special features | integr. power supply for strain gauge 0.5…5 V, parameterizable, ExtendedRange 107%, free numeric filter, TrueRMS, integrator/differentiator, non-linear scaling, PeakHold, with calibration certificate |
| Operating/storage temperature | 0…+55°C/-25…+85°C |
| Weight | approx. 65В g |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Approvals/markings | CE, UL, ATEX, IECEx |
| Protect. rating/installation pos. | IP20/variable |
| Ex marking | ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc |