Technical dataEL3602-0002
Number of inputs 2 (differential)
Power supply via the E-bus
Signal voltage -200…+200 mV
Oversampling factor –
Input signal bandwidth –
Distributed clocks –
Distributed clock precision –
Internal resistance > 200 kО©
Input filter limit frequency 10 kHz
Common-mode voltage UCM max. 35 V
Conversion time 20 ms default setting, 1…400 ms configurable
Resolution 24 bit (incl. sign)
Measurement error/uncertainty
Electrical isolation 500 V (E-bus/signal voltage)
Current consumption power contacts –
Current consumption E-bus typ. 190 mA
Crosstalk attenuation > 60 dB
Special features various filter times, limit value monitoring, high precision
Operating/storage temperature 0…+55°C/-25…+85°C
Weight approx. 60 g
Relative humidity 95%, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Approvals/markings CE, UL, ATEX, IECEx
Protect. rating/installation pos. IP20/variable
Ex marking ATEX:
II 3 G Ex ec IIC T4 Gc
IECEx:
Ex ec IIC T4 Gc