| Number of inputs | 3 x current, 3 x voltage |
| Oversampling factor | – |
| Distributed clocks | – |
| Update interval | > 10 s |
| Measured values | energy, power, power quality factor |
| Measuring voltage | max. 480 V AC 3~ (ULX-N: max. 277 V AC/240 V DC) |
| Measuring current | max. 1 A (AC/DC), via measuring transformers xВ A/1В A |
| Measurement error/uncertainty | 0.5% relative to full scale value (U/I), 1% calculated value |
| Update time | net-synchronous |
| Monitoring function | phase order, phase failure, phase asymmetry, undervoltage/overvoltage (adjustable) |
| Electrical isolation | 2500 V |
| Current consumption power contacts | – |
| Current consumption E-bus | typ. 120 mA |
| Special features | mains monitoring, optional single-phase operation |
| Operating/storage temperature | -25…+60°C/-40…+85°C |
| Weight | approx. 75 g |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Approvals/markings | CE |